Apcupsd, a daemon for controlling APC UPSes
Apcupsd can be used for power mangement and controlling most of APC's UPS models on Unix and Windows machines. Apcupsd works with most of APC's Smart-UPS models as well as most simple signalling models such a Back-UPS, and BackUPS-Office. During a power failure, apcupsd will inform the users about the power failure and that a shutdown may occur. If power is not restored, a system shutdown will follow when the battery is exhausted, a timeout (seconds) expires, or runtime expires based on internal APC calculations determined by power consumption rates. Apcupsd is licensed under the GPL version 2.
Мой файл настроек /etc/apcupsd/apcupsd.conf
в Kubuntu 7.10 для APC Back-UPS ES 700VA:
# # for apcupsd release 3.14.1 (04 May 2007) - debian # # "apcupsd" POSIX config file # # ========= General configuration parameters ============ # # UPSNAME xxx # Use this to give your UPS a name in log files and such. This # is particulary useful if you have multiple UPSes. This does not # set the EEPROM. It should be 8 characters or less. UPSNAME apc700 # UPSCABLE <cable> # Defines the type of cable connecting the UPS to your computer. # # Possible generic choices for <cable> are: # simple, smart, ether, usb # # Or a specific cable model number may be used: # 940-0119A, 940-0127A, 940-0128A, 940-0020B, # 940-0020C, 940-0023A, 940-0024B, 940-0024C, # 940-1524C, 940-0024G, 940-0095A, 940-0095B, # 940-0095C, M-04-02-2000 # #UPSCABLE smart UPSCABLE usb # To get apcupsd to work, in addition to defining the cable # above, you must also define a UPSTYPE, which corresponds to # the type of UPS you have (see the Description for more details). # You must also specify a DEVICE, sometimes referred to as a port. # For USB UPSes, please leave the DEVICE directive blank. For # other UPS types, you must specify an appropriate port or address. # # UPSTYPE DEVICE Description # apcsmart /dev/tty** Newer serial character device, # appropriate for SmartUPS models using # a serial cable (not USB). # # usb <BLANK> Most new UPSes are USB. A blank DEVICE # setting enables autodetection, which is # the best choice for most installations. # # net hostname:port Network link to a master apcupsd # through apcupsd's Network Information # Server. This is used if you don't have # a UPS directly connected to your computer. # # snmp hostname:port:vendor:community # SNMP Network link to an SNMP-enabled # UPS device. Vendor is the MIB used by # the UPS device: can be "APC", "APC_NOTRAP" # or "RFC" where APC is the powernet MIB, # "APC_NOTRAP" is powernet with SNMP trap # catching disabled, and RFC is the IETF's # rfc1628 UPS-MIB. You usually want "APC". # Port is usually 161. Community is usually # "private". # # dumb /dev/tty** Old serial character device for use # with simple-signaling UPSes. # # pcnet ipaddr:username:passphrase # PowerChute Network Shutdown protocol # which can be used as an alternative to SNMP # with AP9617 family of smart slot cards. # ipaddr is the IP address of the UPS mgmt # card. username and passphrase are the # credentials for which the card has been # configured. # #UPSTYPE apcsmart #DEVICE /dev/ttyS0 UPSTYPE usb DEVICE # LOCKFILE <path to lockfile> # Path for device lock file. Not used on Win32. LOCKFILE /var/lock # SCRIPTDIR <path to script directory> # Directory in which apccontrol and event scripts are located. SCRIPTDIR /etc/apcupsd # PWRFAILDIR <path to powerfail directory> # Directory in which to write the powerfail flag file. This file # is created when apcupsd initiates a system shutdown and is # checked in the OS halt scripts to determine if a killpower # (turning off UPS output power) is required. PWRFAILDIR /etc/apcupsd # NOLOGINDIR <path to nologin directory> # Directory in which to write the nologin file. The existence # of this flag file tells the OS to disallow new logins. NOLOGINDIR /etc # # ======== Configuration parameters used during power failures ========== # # The ONBATTERYDELAY is the time in seconds from when a power failure # is detected until we react to it with an onbattery event. # # This means that, apccontrol will be called with the powerout argument # immediately when a power failure is detected. However, the # onbattery argument is passed to apccontrol only after the # ONBATTERYDELAY time. If you don't want to be annoyed by short # powerfailures, make sure that apccontrol powerout does nothing # i.e. comment out the wall. ONBATTERYDELAY 6 # # Note: BATTERYLEVEL, MINUTES, and TIMEOUT work in conjunction, so # the first that occurs will cause the initation of a shutdown. # # If during a power failure, the remaining battery percentage # (as reported by the UPS) is below or equal to BATTERYLEVEL, # apcupsd will initiate a system shutdown. BATTERYLEVEL 5 # If during a power failure, the remaining runtime in minutes # (as calculated internally by the UPS) is below or equal to MINUTES, # apcupsd, will initiate a system shutdown. MINUTES 3 # If during a power failure, the UPS has run on batteries for TIMEOUT # many seconds or longer, apcupsd will initiate a system shutdown. # A value of 0 disables this timer. # # Note, if you have a Smart UPS, you will most likely want to disable # this timer by setting it to zero. That way, you UPS will continue # on batteries until either the % charge remaing drops to or below BATTERYLEVEL, # or the remaining battery runtime drops to or below MINUTES. Of course, # if you are testing, setting this to 60 causes a quick system shutdown # if you pull the power plug. # If you have an older dumb UPS, you will want to set this to less than # the time you know you can run on batteries. TIMEOUT 0 # Time in seconds between annoying users to signoff prior to # system shutdown. 0 disables. ANNOY 300 # Initial delay after power failure before warning users to get # off the system. ANNOYDELAY 60 # The condition which determines when users are prevented from # logging in during a power failure. # NOLOGON <string> [ disable | timeout | percent | minutes | always ] NOLOGON disable # If KILLDELAY is non-zero, apcupsd will continue running after a # shutdown has been requested, and after the specified time in # seconds attempt to kill the power. This is for use on systems # where apcupsd cannot regain control after a shutdown. # KILLDELAY <seconds> 0 disables KILLDELAY 0 # # ==== Configuration statements for Network Information Server ==== # # NETSERVER [ on | off ] on enables, off disables the network # information server. If netstatus is on, a network information # server process will be started for serving the STATUS and # EVENT data over the network (used by CGI programs). NETSERVER on # NISIP <dotted notation ip address> # IP address on which NIS server will listen for incoming connections. # This is useful if your server is multi-homed (has more than one # network interface and IP address). Default value is 0.0.0.0 which # means any incoming request will be serviced. Alternatively, you can # configure this setting to any specific IP address of your server and # NIS will listen for connections only on that interface. Use the # loopback address (127.0.0.1) to accept connections only from the # local machine. NISIP 127.0.0.1 # NISPORT <port> default is 3551 as registered with the IANA # port to use for sending STATUS and EVENTS data over the network. # It is not used unless NETSERVER is on. If you change this port, # you will need to change the corresponding value in the cgi directory # and rebuild the cgi programs. NISPORT 3551 # If you want the last few EVENTS to be available over the network # by the network information server, you must define an EVENTSFILE. EVENTSFILE /var/log/apcupsd.events # EVENTSFILEMAX <kilobytes> # By default, the size of the EVENTSFILE will be not be allowed to exceed # 10 kilobytes. When the file grows beyond this limit, older EVENTS will # be removed from the beginning of the file (first in first out). The # parameter EVENTSFILEMAX can be set to a different kilobyte value, or set # to zero to allow the EVENTSFILE to grow without limit. EVENTSFILEMAX 10 # # ========== Configuration statements used if sharing ============= # a UPS with more than one machine # NETTIME <int> # Interval (in seconds) at which the NIS client polls the server. # Used only when this apcupsd is a network client (UPSTYPE net). #NETTIME 60 # # Remaining items are for ShareUPS (APC expansion card) ONLY # # UPSCLASS [ standalone | shareslave | sharemaster ] # Normally standalone unless you share an UPS using an APC ShareUPS # card. UPSCLASS standalone # UPSMODE [ disable | share ] # Normally disable unless you share an UPS using an APC ShareUPS card. UPSMODE disable # # ===== Configuration statements to control apcupsd system logging ======== # # Time interval in seconds between writing the STATUS file; 0 disables STATTIME 0 # Location of STATUS file (written to only if STATTIME is non-zero) STATFILE /var/log/apcupsd.status # LOGSTATS [ on | off ] on enables, off disables # Note! This generates a lot of output, so if # you turn this on, be sure that the # file defined in syslog.conf for LOG_NOTICE is a named pipe. # You probably do not want this on. LOGSTATS off # Time interval in seconds between writing the DATA records to # the log file. 0 disables. DATATIME 0 # FACILITY defines the logging facility (class) for logging to syslog. # If not specified, it defaults to "daemon". This is useful # if you want to separate the data logged by apcupsd from other # programs. #FACILITY DAEMON # # ========== Configuration statements used in updating the UPS EPROM ========= # # # These statements are used only by apctest when choosing "Set EEPROM with conf # file values" from the EEPROM menu. THESE STATEMENTS HAVE NO EFFECT ON APCUPSD. # # UPS name, max 8 characters #UPSNAME UPS_IDEN # Battery date - 8 characters #BATTDATE mm/dd/yy # Sensitivity to line voltage quality (H cause faster transfer to batteries) # SENSITIVITY H M L (default = H) #SENSITIVITY H # UPS delay after power return (seconds) # WAKEUP 000 060 180 300 (default = 0) #WAKEUP 60 # UPS Grace period after request to power off (seconds) # SLEEP 020 180 300 600 (default = 20) #SLEEP 180 # Low line voltage causing transfer to batteries # The permitted values depend on your model as defined by last letter # of FIRMWARE or APCMODEL. Some representative values are: # D 106 103 100 097 # M 177 172 168 182 # A 092 090 088 086 # I 208 204 200 196 (default = 0 => not valid) #LOTRANSFER 208 # High line voltage causing transfer to batteries # The permitted values depend on your model as defined by last letter # of FIRMWARE or APCMODEL. Some representative values are: # D 127 130 133 136 # M 229 234 239 224 # A 108 110 112 114 # I 253 257 261 265 (default = 0 => not valid) #HITRANSFER 253 # Battery charge needed to restore power # RETURNCHARGE 00 15 50 90 (default = 15) #RETURNCHARGE 15 # Alarm delay # 0 = zero delay after pwr fail, T = power fail + 30 sec, L = low battery, N = never # BEEPSTATE 0 T L N (default = 0) #BEEPSTATE T # Low battery warning delay in minutes # LOWBATT 02 05 07 10 (default = 02) #LOWBATT 2 # UPS Output voltage when running on batteries # The permitted values depend on your model as defined by last letter # of FIRMWARE or APCMODEL. Some representative values are: # D 115 # M 208 # A 100 # I 230 240 220 225 (default = 0 => not valid) #OUTPUTVOLTS 230 # Self test interval in hours 336=2 weeks, 168=1 week, ON=at power on # SELFTEST 336 168 ON OFF (default = 336) #SELFTEST 336
Посмотреть отчет по работе демона apcupsd можно, просмотрев /var/log/apcupsd.events
, например командой tail /var/log/apcupsd.events
(вырезал кусок лога, который информирует об отключении питания и выключении системы после 15-ти минут работы от батарей):
Sun Jan 27 11:46:45 MSK 2008 Power failure. Sun Jan 27 11:46:51 MSK 2008 Running on UPS batteries. Sun Jan 27 12:00:56 MSK 2008 Reached remaining time percentage limit on batteries. Sun Jan 27 12:00:56 MSK 2008 Initiating system shutdown! Sun Jan 27 12:00:56 MSK 2008 User logins prohibited Sun Jan 27 12:01:09 MSK 2008 apcupsd exiting, signal 15 Sun Jan 27 12:01:09 MSK 2008 apcupsd shutdown succeeded